Surge arrester type 1+2, ETITEC V B T12 280/12.5 4+0 RC, (TN-S)
In Stock
Delivered Tomorrow
Delivered Tomorrow
21
Stock Availability
21 Piece Still in Stock
External Warehouse
Available Between Fri 18.04 and Fri 18.04
More than 30 Piece Available in External Warehouse
Item number:
64305
Manufacturer number:
002442917
EAN:
3838895828235
Your advantages with Normrahmen AG
Free shipping from 79 CHFwithin Switzerland
Production & Developmenthigh quality products
Everything from a single source60 day return policy
Attractive cost advantagesthanks to our own production
Product information "Surge arrester type 1+2, ETITEC V B T12 280/12.5 4+0 RC, (TN-S) "
One device 2 protection levels
The great advantage of the combined arrester is that lightning equipotential bonding and terminal device protection are provided in one device in one protection level. They are suitable for discharging high partial lightning currents and limiting transient overvoltages. The combined arresters have an energetically coordinated protective effect to the equipment within a 10 m cable path. If this is exceeded, further protective measures should be taken. Dangerous sparking and transient overvoltages in the electrical system are prevented, thereby avoiding major damage to property.
Combined arresters T1-T2 are type 1 and type 2 protective devices tested in accordance with the test standard DIN EN 61643-11 (VDE 0675 Part 6-11). Their task is to control high energies, safely divert lightning currents and limit dangerous transient overvoltages to a level that is compatible with the equipment.
In addition, type 1 or combi T1 & T2 surge arresters are also suitable for external lightning protection systems. (External lightning protection)
The great advantage of the combined arrester is that lightning equipotential bonding and terminal device protection are provided in one device in one protection level. They are suitable for discharging high partial lightning currents and limiting transient overvoltages. The combined arresters have an energetically coordinated protective effect to the equipment within a 10 m cable path. If this is exceeded, further protective measures should be taken. Dangerous sparking and transient overvoltages in the electrical system are prevented, thereby avoiding major damage to property.
Combined arresters T1-T2 are type 1 and type 2 protective devices tested in accordance with the test standard DIN EN 61643-11 (VDE 0675 Part 6-11). Their task is to control high energies, safely divert lightning currents and limit dangerous transient overvoltages to a level that is compatible with the equipment.
In addition, type 1 or combi T1 & T2 surge arresters are also suitable for external lightning protection systems. (External lightning protection)
Item number: | 64305 |
---|---|
Manufacturer number: | 002442917 |
Applied technology: | MOV |
I imp (10/350) Pulse current: | 12.5kA |
I max (8/20): | 50kA |
In (8/20): | 20kA |
Interchangeable surge modules: | Yes |
Leakage current free: | No |
Net shape: | TN-S |
---|---|
No back-up fuse required until: | 125A |
Type: | T1 & T2 |
Uc Continuous operating voltage: | 280V |
Up - Voltage protection level: | < 1.5kV |
With remote signalling contact: | Yes |